7.14 Y: Application Features
No.
Name
(Hex.)
YF-03
PI Aux Control Setpoint
(3F52)
RUN
YF-04
PI Aux Control Minimum
Level
(3F53)
RUN
YF-05
PI Aux Control Sleep Delay
Time
(3F54)
RUN
YF-06
PI Aux Control Wake-up
Level
(3F55)
RUN
YF-07
PI Aux Control Wake-up
Time
(3F56)
YF-08
PI Aux Control Minimum
Speed
(3F57)
RUN
YF-09
PI Aux Control Low Level
Detect
(3F58)
RUN
YF-10
PI Aux Low Level Detection
Time
(3F59)
RUN
YF-11
PI Aux Control Low Level
Det Sel
(3F5A)
YF-12
PI Aux Control High Level
Detect
(3F5B)
RUN
YF-13
PI Aux High Level
Detection Time
(3F5C)
RUN
240
Sets the level to which the drive will try to regulate.
Note:
Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level Decimal Place
Pos] set the unit and resolution.
Sets the level below which the drive must be for longer than YF-05 [PI Aux Control Sleep Delay
Time] before the drive goes to sleep and turns off all lag pumps.
Note:
• Set this parameter to 0.0 to disable the function.
• Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level Decimal Place
Pos] set the unit and resolution.
Sets the length of time that the drive will delay before it goes to sleep after the level is less than YF-
04 [PI Aux Control Minimum Level] (when YF-23 = 1 [PI Aux Ctrl Output Level Select = Inverse
Acting]) or more than YF-24 [PI Auxiliary Ctrl Maximum Level] (when YF-23 = 0 [Direct Acting]).
Sets the level to wake up the drive when the drive after YF-04 [PI Aux Control Minimum Level] or
YF-24 [PI Auxiliary Ctrl Maximum Level] put the drive to sleep.
Note:
• Parameter YF-23 [PI Aux Ctrl Output Level Select] sets the condition to wake up the drive.
–YF-23 = 0 [Direct Acting]: The PI Aux Feedback must be less than the level set in this
parameter for longer than the time set in YF-07 to wake up.
–YF-23 = 1 [Inverse Acting]: The PI Aux Feedback must be more than the level set in this
parameter for longer than the time set in YF-07 [PI Aux Control Wake-up Time] to wake up.
• Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level Decimal Place
Pos] set the unit and resolution.
Sets the time to wake up the drive when the drive after YF-04 [PI Aux Control Minimum Level] or
YF-24 [PI Auxiliary Ctrl Maximum Level] put the drive to sleep.
Note:
Parameter YF-23 [PI Aux Ctrl Output Level Select] sets the condition to wake up the drive.
• YF-23 = 0 [Direct Acting]: The PI Aux Feedback must be less than the level set in YF-06 for
longer than the time set in YF-07 to wake up.
• YF-23 = 1 [Inverse Acting]: The PI Aux Feedback must be more than the level set in YF-06 [PI
Aux Control Wake-up Level] for longer than the time set in YF-07 to wake up.
Sets the minimum speed at which the drive can run when the PI Auxiliary Control has an effect on
the output speed.
Note:
The drive will use Y1-06 [Minimum Speed] and Y4-12 [Thrust Frequency] as the minimum speed
when PI Aux Control does not have an effect on the output speed or when you set YF-08 < Y1-06
and Y4-12.
Sets the level below which the drive must be for longer than YF-10 [PI Aux Control Low Lvl Det
Time] to respond as specified by YF-11 [PI Aux Control Low Level Det Sel].
Note:
• Set this parameter to 0.0 to disable the function.
• Parameter YF-10 only applies to when YF-11 = 2 and 3 [Fault and Auto-Restart (time set by
YF-15)].
• Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level Decimal Place
Pos] set the unit and resolution.
Sets the length of time that the PI Aux Feedback must be less than YF-09 [PI Aux Control Low Lvl
Detection] to trigger a drive response when YF-11 = 2 and 3 [PI Aux Control Low Level Det Sel =
Fault and Auto-Restart (time set by YF-15)].
Sets drive response when the PI Aux Feedback decreases to less than YF-09 [PI Aux Control Low Lvl
Detection] for longer than YF-10 [PI Aux Control Low Lvl Det Time].
0 : No Display
1 : Alarm Only
2 : Fault
3 : Auto-Restart (time set by YF-15)
Note:
• Set YF-01 = 1 [PI Aux Control Selection = Enabled] and YF-09 [PI Aux Control Low Level
Detect] > 0 to enable PI Aux Low Level Detection.
• Parameter YF-10 only applies when YF-11 = 2 or 3.
Sets the value above which the level must be for longer than YF-13 [PI Aux High Level Detection
Time] to respond as specified by YF-14 [PI Aux Hi Level Detection Select].
Note:
• Set this parameter to 0.0 to disable the function.
• Parameter YF-13 only applies to when YF-14 = 2 and 3 [Fault and Auto-Restart (time set by
YF-15)].
• Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level Decimal Place
Pos] set the unit and resolution.
Sets the length of time that the level must be more than YF-12 [PI Aux Control High Level Detect]
before the drive will respond when YF-14 = 2, 3 [PI Aux Hi Level Detection Select].
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Description
Default
(Range)
20.0 PSI
(0.0 - 6000.0)
10.0 PSI
(0.0 - 6000.0)
5 s
(0 - 3600 s)
30.0 PSI
(-999.9 - +999.9 PSI)
1 s
(0 - 3600 s)
0.00 Hz
(0.00 - 400.00 Hz)
0.0 PSI
(-999.9 - +999.9 PSI)
0.1 s
(0.0 - 300.0 s)
1
(0 - 3)
0.0 PSI
(-999.9 - +999.9 PSI)
0.1 s
(0.0 - 300.0 s)