YASKAWA HV600 Installation & Startup page 111

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Code
Name
CPF33
Watch-dog Eror
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF34
Power/Clock Eror
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF35
Ext A/D Conv Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF36
ASIC COM Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF37
ASIC COM Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF38
EEPROM Memory Data Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
CPF39
CPU-ASIC Communication Error
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
Code
Name
dEv
Speed Deviation
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
A drive hardware problem occurred.
Causes
The load is too heavy.
Acceleration and deceleration times are set too short.
The dEv detection level settings are incorrect.
The load is locked up.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
Decrease the load.
Increase the values set in C1-01 to C1-04 [Acceleration/
Deceleration Time].
Adjust F1-10 [Speed Deviation Detection Level] and F1-11 [Speed
Deviation Detect DelayTime].
Examine the machine.
5.5 Faults
5
111

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents