L3: Stall Prevention
No.
Name
(Hex.)
L3-01
Stall Prevention during
Accel
(048F)
L3-02
Stall Prevent Level during
Accel
(0490)
L3-03
Stall Prevent Limit during
Accel
(0491)
L3-04
Stall Prevention during
Decel
(0492)
L3-05
Stall Prevention during RUN Sets the function to enable and disable Stall Prevention During Run.
(0493)
L3-06
Stall Prevent Level during
Run
(0494)
L3-11
Overvoltage Suppression
Select
(04C7)
L3-17
DC Bus Regulation Level
(0462)
L3-20
DC Bus Voltage Adjustment
Gain
(0465)
Expert
L3-21
OVSuppression Accel/Decel
P Gain
(0466)
Expert
L3-23
Stall P Reduction at
Constant HP
(04FD)
L3-24
Motor Accel Time @ Rated
Torque
(046E)
Expert
L3-25
Load Inertia Ratio
(046F)
Expert
L3-26
Additional DC Bus
Capacitors
(0455)
Expert
L3-27
Stall Prevention Detection
Time
(0456)
L3-35
Speed Agree Width for Auto
Decel
(0747)
Expert
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Sets the method of Stall Prevention During Acceleration.
0 : Disabled
1 : Enabled
2 : Intelligent (Ignore Decel Ramp)
Sets the output current level to activate the Stall Prevention function during acceleration as a
percentage of the drive rated output current.
Sets the lower limit for the stall prevention level used in the constant output range as a percentage of
the drive rated output current.
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
0 : Disabled
1 : General Purpose
2 : Intelligent (Ignore Decel Ramp)
4 : Overexcitation/High Flux
Note:
An output frequency lower than 6 Hz will disable Stall Prevention during Run. The L3-05 and
L3-06 [Stall Prevent Level during Run] settings do not have an effect.
0 : Disabled
1 : Deceleration Time 1 (C1-02)
2 : Deceleration Time 2 (C1-04)
Sets the output current level to enable the Stall Prevention function during operation as a percentage
of the drive rated output current.
Note:
This parameter is applicable when L3-05 = 1, 2 [Stall Prevention during RUN = Deceleration
Time 1 (C1-02), Deceleration Time 2 (C1-04)].
Sets the overvoltage suppression function.
0 : Disabled
1 : Enabled
Sets the target value for the DC bus voltage when the overvoltage suppression function and the Decel
Stall Prevention function (Intelligent Stall Prevention) are active.
Sets the proportional gain used to control the DC bus voltage.
Sets the proportional gain to calculate acceleration and deceleration rates.
Sets the function to automatically decrease the Stall Prevention Level during Run for constant output
ranges.
0 : Use L3-06 for Entire Speed Range
1 : Automatic Reduction @ CHP Region
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque for
stopped single-drive motors.
Sets the ratio between motor inertia and machine inertia.
Sets the capacity for external main circuit capacitors. Usually it is not necessary to change this
setting.
Sets a delay time between reaching the Stall Prevention level and starting the Stall Prevention
function.
Sets the width for speed agreement when L3-04 = 2 [Decel Stall Prevention Selection = Automatic
Decel Reduction]. Usually it is not necessary to change this setting.
Description
7.9 L: Protection Functions
Default
(Range)
1
(0 - 2)
Determined by L8-38
(0 - 120%)
50%
(0 - 100%)
1
(0 - 4)
2
(0 - 2)
Determined by L8-38
(5 - 120%)
0
(0, 1)
208/240 V: 375 V,
480 V: 750 V
(208/240 V: 150 - 400 V,
480 V: 300 - 800 V)
1.00
(0.00 - 5.00)
1.00
(0.10 - 10.00)
0
(0, 1)
Determined by o2-04, E2-11
(0.001 - 10.000 s)
1.0
(0.1 - 1000.0)
0 μF
(0 to 65000 μF)
50 ms
(0 - 5000 ms)
0.00 Hz
(0.00 - 1.00 Hz)
7
213