Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to
dimensions and model numbers of the crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.
Wire Gauge
mm
2
(AWG)
0.25 (24)
AI 0.25-8YE
0.34 (22)
AI 0.34-8TQ
AI 0.5-8WH
0.5 (20)
AI 0.5-8OG
0.75 (18)
AI 0.75-8 GY
Control Circuit Terminal Block Input Functions
Hx-xx parameters set functions for the multi-function input and output terminals.
WARNING! Sudden Movement Hazard. Correctly wire and test all control circuits to make sure that the control circuits operate
correctly. If you use a drive that has incorrect control circuit wiring or operation, it can cause death or serious injury.
WARNING! Sudden Movement Hazard. Check the I/O signals and the external sequences for the drive before you set the
Application Preset function. When you set the Application Preset function (A1-06 ≠ 0), it changes the I/O terminal functions for the
drive and it can cause equipment to operate unusually. This can cause serious injury or death.
NOTICE: Damage to Equipment. Do not energize and de-energize the bypass more frequently than one time each 30 minutes. If
you frequently energize and de-energize the bypass, it can cause failure.
Refer to
Table 3.13
for a list of input terminals and functions on the drive.
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Figure 3.14 External Dimensions of Crimp Ferrules
Table 3.12 Crimp Ferrule Models and Sizes
Model
L (mm)
12.5
12.5
14
14
3.6 Drive PCB Control Circuit
Table 3.12
for the recommended external
L1 (mm)
φd1 (mm)
8
0.8
8
0.8
8
1.1
8
1.3
φd2 (mm)
2.0
2.0
2.5
2.8
3
55