Type
Terminal
TB2-1
Digital Input 1
DI-1
(Run (AUTO))
TB2-2
Digital Input 2
DI-2
(Run Enable - Safety (NC))
TB2-3
Digital Input 3
DI-3
(Run Interlock (BAS))
TB2-4
Digital Input 4
DI-4
(Remote Transfer to Bypass)
TB2-5
Digital Input 5
Digital Inputs
DI-5
(Emergency Override Bypass)
TB2-6
Digital Input 6
DI-6
(-)
TB2-7
Digital Input 7
DI-7
(-)
TB2-8
Digital Input 8
DI-8
(-)
TB2-9/10
Isolated Ground
IG24
Type
Terminal
TB4-1
Analog Input Power Supply
+10 Vdc
TB4-2
Analog Input
Analog Input Speed Reference
AI
TB4-3
Analog Input Common
COMMON
Bypass Control Circuit Terminal Block Output Functions
Type
Terminal
TB1-1/2/3
Digital Output 7
DO-7
(Motor Run)
TB1-4/5/6
Digital Output 8
DO-8
(HAND Mode)
Digital Outputs
TB1-7/8/9
Digital Output 9
DO-9
(AUTO Mode)
TB1-10/11/
Digital Output 10
12
(System Fault)
DO-10
Type
Terminal
TB6-1/2
Ground
Chassis Ground
GROUND
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Table 3.5 Bypass Digital Input Terminals (TB2)
Name (Default)
Dry contact rated, photocoupler sinking input to IG24, 24 Vdc 8 mA,
Ground fault protected
Digital input common
Table 3.6 Bypass Analog Input Terminals (TB4)
Name (Default)
AUTO Mode
Speed Reference
0 to 10 Vdc (20 kΩ) or 4 to 20 mA (250 Ω)
Table 3.7 Bypass Digital Output Terminals (TB1)
Name (Default)
Relay, dry contact form C, 30 Vdc or 120 Vac,
DO-7 to DO-10 for customer use, 2 Amp
Table 3.8 Control Circuit Ground Terminals (TB6)
Name (Default)
-
3.5 Bypass PCB Control Circuit
Function (Signal Level)
Function (Signal Level)