YASKAWA HV600 Installation & Startup page 227

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
S2-13
Timer 3 Day Selection
(3212)
S2-14
Timer 3 Sequence Selection
(3213)
S2-15
Timer 3 Reference Source
(3214)
S2-16
Timer 4 Start Time
(3215)
S2-17
Timer 4 Stop Time
(3216)
S2-18
Timer 4 Day Selection
(3217)
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Sets the days for which sequence timer 3 is active.
0 : Timer Disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
Sets the drive response when sequence timer 3 is active.
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
Selects the frequency reference source to run the drive when sequence timer 3 is active (only
applicable when S2-14 > 0 [Timer 3 Sequence Selection ≠ Digital Out Only]).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use d1-xx frequency reference when PID mode is
disabled and YA-xx setpoint when PID is enabled.
Sets the start time for timer 4.
Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24 Hour Clock],
default is 00:00. When o4-22 = 2 [12 Hour JP Clock], default is 00:00 AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 = 2, range is
00:00 AM to 11:59 PM.
Sets the stop time for timer 4.
Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24 Hour Clock],
default is 00:00. When o4-22 = 2 [12 Hour JP Clock], default is 00:00 AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 = 2, range is
00:00 AM to 11:59 PM.
Sets the days for which sequence timer 4 is active.
0 : Timer disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
7.12 S: Special Applications
Description
Default
(Range)
0
(0 - 10)
0
(0 - 2)
0
(0 - 8)
12:00
(12:00 AM - 11:59 PM)
12:00
(12:00 AM - 11:59 PM)
0
(0 - 10)
7
227

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents