7.16 U: Monitors
No.
Name
(Hex.)
Ub-05
Bypass Status 1
(8784)
262
0: HAND mode
0: Not in HAND
1: In HAND Mode
1: OFF mode
0: Not in OFF
1: In OFF Mode
2: AUTO mode
0: Not in AUTO
1: In AUTO Mode
3: DRIVE mode (cmnd)
0: Drive mode not commanded
1: Drive mode commanded
4: BYPASS mode (cmnd)
0: Bypass mode not commanded
1: Bypass mode commanded
5: :Emergency override BYP Act
0: Not active
1: :Emergency override bypass is active
6: :Emergency override DRV Act
0: Not active
1: EMOV Drive is active (:Emergency override drive)
7: Safety Open
0: All programmed safeties closed
1: At least one programmed safety open
8: Alarm Active
0: No Alarm
1: Alarm
9: Drive Run active
0: Not running in drive
1: Running in drive mode
10: Bypass run active
0: Not running in bypass
1: Running in bypass mode
11: Emergency override Drive REV
0: running FWD
1: running REV
12: Drive comms active
0: Drive comms Not active
1: Drive comms active
13: System READY
0: Not READY
1: READY
Unit: -