3.6 Drive PCB Control Circuit
Type
Terminal
MFDI selection 1
S1
(Not used)
MFDI selection 2
S2
(Not Used)
MFDI selection 3
S3
(External Fault (NO-Always-Coast))
MFDI selection 4
S4
(Not used)
MFDI selection 5
S5
MFDI
(Multi-Step Speed Reference 1)
MFDI selection 6
S6
(Multi-Step Speed Reference 2)
MFDI selection 7
S7
(Jog Reference Selection)
SN
MFDI power supply 0 V
SC
MFDI selection common
SP
MFDI power supply +24 Vdc
H1
Safe Disable input 1
H2
Safe Disable input 2
Safe Disable
Input
HC
Safe Disable function common
+V
Power supply for frequency setting
A1
MFAI1
Analog
Inputs
A2
MFAI2
AC
Analog input common
FE
Connecting shielded cable
Control Circuit Terminal Block Output Functions
Refer to
Table 3.14
and
Table 3.15
56
Table 3.13 Drive Multi-function Input Terminals
Name (Default)
Multi-Function Digital Input
• Photocoupler
• 24 V, 6 mA
Note:
Install the wire jumpers between terminals SC-SP and SC-SN to set the MFDI power supply
(sinking/sourcing mode or internal/external power supply).
• Sinking Mode: Install a jumper between terminals SC and SP.
• Sourcing Mode: Install a jumper between terminals SC and SN.
• External power supply: No jumper necessary between terminals SC-SN and terminals SC-SP.
MFDI power supply, 24 V (maximum 150 mA)
NOTICE: Damage to Equipment. Do not close the circuit between
terminals SP-SN. If you close the circuits between terminals SC-SP and
terminals SC-SN at the same time, it will cause damage to the drive.
Safe Disable Input
Remove the jumper between terminals H1-HC and H2-HC to use the Safe Disable input.
• 24 V, 6 mA
• ON: Normal operation
• OFF: Coasting motor
• Internal impedance 4.7 kΩ
• OFF Minimum OFF time of 2 ms.
Note:
Safe disable inputs are only effective in Drive Mode. They will not function in Bypass Mode.
Safe Disable function common
NOTICE: Do not close the circuit between terminals HC and SN. A
closed circuit between these terminals will cause damage to the drive.
Power Supply for Multi-Function Analog Input
• 10.5 V (allowable current 20 mA maximum)
Voltage input or current input
Select terminal A1 with Jumper switch S1 and H3-01 [Terminal A1 Signal Level Select].
• 0 V to 10 V/100% (input impedance: 20 kΩ)
• 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
Voltage input or current input
Select terminal A2 with Jumper switch S1 and H3-09 [Terminal A2 Signal Level Select]
• 0 V to 10 V/100% (input impedance: 20 kΩ)
• 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
Signal Ground for Multi-Function Analog Input
• 0 V
Frame Earth
for a list of output terminals and functions.
Function (Signal Level)
NOTICE: Damage to Equipment. Do not close the circuit between
terminals SC-SN. If you close the circuits between terminals SC-SP
and terminals SC-SN at the same time, it will cause damage to the
drive.
NOTICE: Damage to Equipment. Do not close the circuit between
terminals SC-SP. If you close the circuits between terminals SC-SP
and terminals SC-SN at the same time, it will cause damage to the
drive.