YASKAWA HV600 Installation & Startup page 198

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

7.8 H: Terminal Functions
Setting Value
Function
188
!Thermostat Fault
1A8
!PI2 Control Disable
H2: Digital Outputs
No.
Name
(Hex.)
H2-01
Term M1-M2 Function
Selection
(040B)
H2-02
Term M3-M4 Function
Selection
(040C)
H2-03
Term M5-M6 Function
Selection
(040D)
H2-06
Watt Hour Output Unit
Selection
(0437)
H2-07
Modbus Register 1 Address
Select
(0B3A)
H2-08
Modbus Register 1 Bit
Select
(0B3B)
H2-09
Modbus Register 2 Address
Select
(0B3C)
H2-10
Modbus Register 2 Bit
Select
(0B3D)
H2-40
Mbus Reg 15E0h bit0
Output Func
(0B58)
H2-41
Mbus Reg 15E0h bit1
Output Func
(0B59)
H2-42
Mbus Reg 15E0h bit2
Output Func
(0B5A)
H2-60
Term M1-M2 Secondary
Function
(1B46)
Expert
H2-61
Terminal M1-M2 Logical
Operation
(1B47)
Expert
H2-62
Terminal M1-M2 Delay
Time
(1B48)
Expert
H2-63
Term M3-M4 Secondary
Function
(1B49)
Expert
198
Sets the drive to show the VLTS [Thermostat Fault] when the input terminal is OFF.
Note:
This function is active when the drive is running.
Sets the command to disable the PI2 Control function. Parameter S3-12 [PI2 Control Disable Mode Sel] sets the output
performance.
ON : Disabled
OFF : Enabled
Sets the function for MFDO terminal M1-M2.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through
mode.
Sets the function for MFDO terminal M3-M4.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through
mode.
Sets the function for MFDO terminal M5-M6.
Note:
When you do not use this terminal, or when you will use the terminal in through mode, set this
parameter to F.
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
Sets the second function for terminal M1-M2. Outputs the logical calculation results of the terminals
assigned to functions by H2-01 [Term M1-M2 Function Selection].
Sets the logical operation for the functions set in H2-01 [Term M1-M2 Function Selection] and H2-
60 [Term M1-M2 Secondary Function].
Sets the minimum on time used to output the logical calculation results from terminal M1-M2.
Sets the second function for terminal M3-M4. Outputs the logical calculation results of the terminals
assigned to functions by H2-02 [Term M3-M4 Function Selection].
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Description
Description
Default
(Range)
0
(0 - 1FF)
1
(0 - 1FF)
2
(0 - 1FF)
0
(0 - 4)
0001
(0001 - 1FFF)
0000
(0000 - FFFF)
0001
(0001 - 1FFF)
0000
(0000 - FFFF)
F
(0 - 1FF)
F
(0 - 1FF)
F
(0 - 1FF)
F
(0 - FF)
0
(0 - 8)
0.1 s
(0.0 - 25.0 s)
F
(0 - FF)