Advertisement

5.4 Faults, Minor Faults, Alarms, and Error Codes Listed by Decimal Value for Use with BACnet/Modbus

5.4
Faults, Minor Faults, Alarms, and Error Codes Listed by
Decimal Value for Use with BACnet/Modbus
Table 5.3
shows the list of faults by decimal number.
Table 5.4
shows the list of minor faults and alarms by decimal number. Minor fault and alarm decimal numbers are
read in Modbus register 007F.
The display codes are in decimal order. Search the tables for the decimal code, and identify its causes and possible
solutions.
Drive Faults thrown by the HV600 drive will stop the bypass from running the drive but will not stop it from running
in Bypass Mode.
System Faults will stop the drive and also stop it from running in Bypass Mode.
Note:
The number in parentheses adjacent to the code in the table identifies the fault code or minor fault code (hex. number) that was read during
MEMOBUS/Modbus communications.
Example: AFBL (00A2)
Decimal Value
Display (Hex.)
2
Uv1 (0002)
3
Uv2 (0003)
4
Uv3 (0004)
5
SC (0005)
6
GF (0006)
7
oC (0007)
8
ov (0008)
9
oH (0009)
10
oH1 (000A)
11
oL1 (000B)
12
oL2 (000C)
13
oL3 (000D)
14
oL4 (000E)
17
EF3 (0011)
18
EF4 (0012)
19
EF5 (0013)
20
EF6 (0014)
21
EF7 (0015)
25
dEv (0019)
27
PF (001B)
28
LF (001C)
29
oH3 (001D)
30
oPr (001E)
31
Err (001F)
32
oH4 (0020)
33
CE (0021)
34
bUS (0022)
39
EF0 (0027)
100
Table 5.3 List of Faults by Decimal
Name
DC Bus Undervoltage
Control Power Undervoltage
Soft Charge Answerback Fault
Short Circuit/IGBT Failure
Ground Fault
Overcurrent
Overvoltage
Heatsink Overheat
Heatsink Overheat
Motor Overload
Drive Overload
Overtorque Detection 1
Overtorque Detection 2
External Fault (Terminal S3)
External Fault (Terminal S4)
External Fault (Terminal S5)
External Fault (Terminal S6)
External Fault (Terminal S7)
Speed Deviation
Input Phase Loss
Output Phase Loss
Motor Overheat (PTC Input)
Keypad Connection Fault
EEPROM Write Error
Motor Overheat Fault (PTC Input)
Modbus Communication Error
Option Communication Error
Option Card External Fault
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
ALM LED
Type
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Illuminated
Drive Fault
Ref.
128
128
129
127
116
118
126
122
123
123
124
125
125
112
113
113
113
113
111
126
117
123
125
113
123
106
106
112