No.
Name
(Hex.)
S6-04
EMOVR Independent PID
Unit
(323B)
S6-05
EMOVR Independent PID
Unit Digit
(323C)
S6-06
EMOVR PID Setpoint
(323D)
RUN
S6-07
EMOVR Fault Suppression
Mode
(323E)
S6-08
EMOVR Drive Enable Input
Mode
(323F)
S6-09
Emergency Override Min
Speed
(3240)
S6-10
Emergency Override Max
Speed
(3241)
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Sets the units displayed for S6-06 [EMOVR PID Setpoint] when S6-02 = 3 [Emergency Override Ref
Selection = Independent PID Mode].
0 : "WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
3
5 : m
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : "Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(b5-68~70)
50 : None
Sets the number of digits for S6-06 [EMOVR PID Setpoint] when S6-02 = 3[Emergency Override
Ref Selection = Independent PID Mode].
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
Sets the PID Setpoint when S6-02 = 3[Emergency Override Ref Selection = Independent PID Mode].
Note:
When S6-02 = 3: units and resolution are dependent on S6-04 [EMOVR Independent PID Unit]
and S6-05 [EMOVR Independent PID Unit Digit]. Value is internally limited to 300% of S6-03
[EMOVR Independent PID Scale].
Sets the drive to let Emergency Override disable faults during operation.
0 : Fault Suppression
1 : Test Mode
Sets whether the Drive Enable Input (if programmed) must be inactive (drive is disabled) for
Emergency Override to function.
0 : Drive Enable Status Ignored
1 : EMOVRun Only When Drive Disabled
Note:
You must program Drive Enable to a Digital Input for this parameter to have an effect.
When Emergency Override is active, the output frequency is lower-limited to this value.
When Emergency Override is active, the output frequency is upper-limited to this value.
Note:
Set this parameter to 0.00 Hz to disable the limit.
7.12 S: Special Applications
Description
Default
(Range)
48
(0 - 50)
2
(0 - 3)
0.00
(0 - 600.00)
0
(0, 1)
0
(0, 1)
0.00 Hz
(0.00 - 400.00 Hz)
0.00 Hz
(0.00 - 400.00)
7
231