Auto Led And Hand Led Indications - YASKAWA HV600 Installation & Startup

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Symbol
Name
D
Mode display area
Alarm codes and status messages
E
display area
Frequency reference source
F
indication
G
Data display area
H
Function keys 1 to 3 (F1 to F3)
Alarm and message texts display
I
area
HOA mode or alternative Run
J
command source indication

AUTO LED and HAND LED Indications

AUTO LED
HAND LED
OFF
OFF
OFF
ON
OFF
Long blink (50% duty) HAND Mode
OFF
Double blink
ON
OFF
Long blink (50% duty)
OFF
Double blink
OFF
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Shows the name of the current mode or screen.
Shows an alarm code or message about bypass status.
Refer to page
151
for more information about status messages.
Shows the current frequency reference source.
• KPD: keypad
• AI: analog input terminal (terminals A1 or A2)
• COM: serial communications
• OPT: option card
Shows parameter values, monitor values, and details of the results of operations.
The function names shown in this area will change when the selected screen changes. Push one of the function keys
on the keypad to do the function.
Shows a fault, minor fault, alarm, or error name and message text.
Note:
When the drive must show an alarm and a message on the keypad at the same time, the keypad will switch between the
alarm code and message text in 2-second intervals.
• OFF: The bypass is operating in OFF Mode.
• AUTO: The bypass is operating in AUTO Mode.
• HAND: The bypass is operating in HAND Mode.
• JOG: The bypass is operating in JOG Mode.
• EMOV: The bypass is operating in Emergency Override Mode.
Table 4.3 AUTO LED and HAND LED Indications
OFF Mode
HAND Mode
• When the Frequency Reference is 0 or during deceleration
• During PI Sleep
HAND Mode
When you clear the Run command and enter the Run command again during the time set in C1-02 [Deceleration Time 1]
AUTO Mode
AUTO Mode
• When the Frequency Reference is 0 or during deceleration
• During PI Sleep
AUTO Mode
When an MFDI sends a Fast Stop signal to stop the drive
Figure 4.3 AUTO LED and HAND LED Timing Status
4.2 Keypad: Names and Functions
Description
Status
to
4
75

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents