T: Motor Tuning - YASKAWA HV600 Installation & Startup

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

7.13 T: Motor Tuning

7.13

T: Motor Tuning

T0: Tuning Mode Selection
No.
Name
(Hex.)
T0-00
Tuning Mode Selection
(1197)
T1: Induction Motor Auto-Tuning
No.
Name
(Hex.)
T1-01
Auto-Tuning Mode Selection Sets the type of Auto-Tuning.
(0701)
T1-02
Motor Rated Power
(0702)
T1-03
Motor Rated Voltage
(0703)
T1-04
Motor Rated Current
(0704)
T1-05
Motor Base Frequency
(0705)
T1-06
Number of Motor Poles
(0706)
T1-07
Motor Base Speed
(0707)
T1-11
Motor Iron Loss
(070B)
234
Sets the type of Auto-Tuning.
0 : Motor Parameter Tuning
0 : Rotational Auto-Tuning
2 : Stationary Line-Line Resistance
Uses the units set in o1-58 [Motor Power Unit Selection] to set the motor rated output power.
Sets the rated voltage (V) of the motor. Enter the base speed voltage for constant output motors.
Sets the rated current (A) of the motor.
Sets the base frequency (Hz) of the motor.
Sets the number of motor poles.
Sets the motor base speed for Auto-Tuning (min
Sets the iron loss for calculating the energy-saving coefficient.
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Description
Description
-1
(r/min)).
Default
(Range)
0
(0)
Default
(Range)
0
(0, 2)
Determined by o2-04
(0.00 - 650.00 HP)
Determined by o2-04
(208/240 V: 0.0 - 255.5 V,
480 V: 0.0 - 511.0 V)
Determined by o2-04
(10% to 200% of the drive
rated current)
60.0 Hz
(0.0 - 400.0 Hz)
4
(2 to 120)
1750 min
-1
(r/min)
-1
(0 - 24000 min
(r/min))
Determined by E2-11
(0 - 65535 W)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents