U: Monitors; U1: Operation Status Monitors - YASKAWA GA500 GA50U Series Programming Manual

Table of Contents

Advertisement

1.17

U: Monitors

U1: Operation Status Monitors

No.
Name
(Hex.)
U1-01
Frequency Reference
(0040)
U1-02
Output frequency
(0041)
U1-03
Output Current
(0042)
U1-04
Control method selection
(0043)
U1-05
Motor Speed
(0044)
U1-06
Output Voltage Ref
(0045)
U1-07
DC Bus Voltage
(0046)
U1-08
Output Power
(0047)
U1-09
Torque Reference
(0048)
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the frequency reference value. Parameter o1-03 [Keypad Display Unit Selection] sets the
display units.
Unit: 0.01 Hz
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the output frequency. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.
Unit: 0.01 Hz
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the actual output current.
The keypad shows the value of U1-03 in amperes (A). When looking at the monitor through
MEMOBUS/Modbus communications, the current is "8192 = drive rated current (A)". Calculate the
current from the monitor value that is in at MEMOBUS/Modbus communications using "Numerals
being displayed / 8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
• 0.01 A units: B001 - B018, 2001 - 2042, 4001 - 4023
• 0.1A units: 2056 - 2082, 4031 - 4060
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the drive control method.
0 : V/f Control
2 : Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
8 : EZ Vector Control
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the detected motor speed. Parameter o1-03 [Keypad Display Unit Selection] sets the display
units.
Unit: 0.01 Hz
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the output voltage reference.
Unit: 0.1 V
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the DC bus voltage.
Unit: 1 V
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the internally-calculated output power.
When you change A1-02 [Control Method Selection], it will also change the signal level of the
analog output.
• A1-02 = 0: Drive capacity (kW)
• A1-02 = 2: Motor Rated Power [E2-11] (kW)
• A1-02 = 5, 6: PM Motor Rated Power [E5-02] (kW)
• A1-02 = 8: Motor Rated Power [E9-07] (kW)
Unit: When the drive model changes, the display units for this parameter also change.
• 0.01 kW: B001 - B018, 2001 - 2042, 4001 - 4023
• 0.1 kW: 2056 - 2082, 4031 - 4060
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the internal torque reference value.
Unit: 0.1%
Description

1.17 U: Monitors

MFAO Signal Level
10 V = Maximum frequency
(0 V to +10 V)
10 V = Maximum frequency
(0 V to +10 V)
10 V = Drive rated current
No signal output available
10 V = Maximum frequency
(0 V to +10 V)
200 V Class: 10 V = 200
Vrms
400 V Class: 10 V = 400
Vrms
200 V Class: 10 V = 400 V
400 V Class: 10 V = 800 V
10 V: Drive capacity (motor
rated power) kW
(0 V to +10 V)
1
10 V = Motor rated torque (0
V to +10 V)
109