Communicate with PanelView and RSView Products
Determine Connections to
PanelView Terminals
Publication CNET-UM001C-EN-P - November 2005
The Logix5000 controller in the local chassis can be any of the following, with
their ControlNet communication modules:
• 1756 ControlLogix controller with a 1756-CN2 or 1756-CN2R
communication module in the chassis
• 1756 ControlLogix controller with a 1756-CNB or 1756-CNBR
communication module in the chassis
• 1769-L32C or 1769-L35CR CompactLogix controller
• 1789 SoftLogix controller with a 1784-PCIC, 1784-PCICS or
1784-PKTCS communication card
• 1794 FlexLogix controller with a 1788-CNx ControlNet communication
card
• PowerFlex 700S with DriveLogix controller and a 1788-CNx
ControlNet communication card
Make sure that:
• the ControlNet communication modules are connected to a scheduled
ControlNet network.
• all wiring and cabling is properly connected.
How you establish communication between a PanelView or PanelView Plus
terminal and a Logix5000 controller over ControlNet depends on how you
want to use controller connections.
Type of Communication
Scheduled (always connected)
Unscheduled connected
Unscheduled unconnected
A Logix controller supports up to 40 outgoing and 3 incoming unconnected
buffers. This limited number of incoming unconnected buffers limits how
many PanelView Standard terminals can request data from a controller.
Terminal Type
PanelView Standard PanelView Plus
Supported
Supported in
version 3.2 and greater
Not supported
Supported
Supported
Not supported