5-12
Produce and Consume Tags (Interlock Controllers)
Additional Steps for a
PLC-5C or ControlNet
Scanner Card
Publication CNET-UM001C-EN-P - November 2005
Some devices connect to the ControlNet network via a ControlNet scanner
and can use produced and consumed tags to share scheduled data with
Logix5000 controllers. For example, you can connect a real-time control
application, such as a Visual Basic application, to ControlNet through a
1784-PKTCS scanner card to exchange data with Logix5000 controllers.
When you use produced and consumed tags to exchange data between
Logix5000 controllers and a ControlNet scanner, you must also use the
RSNetWorx Scanlist Configuration Tool to configure the scanner to produce
and consume the data sent to and/or received from the Logix5000 controllers.
The following ControlNet scanners require additional steps to exchange data
with a Logix5000 controller via produced and consumed tags:
• PLC-5C controller
• 1784-PKTCS communication scanner card
– This card is used in a personal computer with a real-time control
application and IOLinx or an HMI application and RSView ME.
• 2711P-RN15S communication scanner card
– This card is used in PanelView Plus and VersaView CE HMI
terminals.
• 2711P-RN15C communication module
– This module is used in a PanelView Plus HMI terminal.