A. Name the module.
B. Select a Comm Format. For more
information on choosing a Comm Format,
see section Communication Format.
C. Select the module's Revision level.
D. Select an Electronic Keying level. For
more information on choosing a keying
level, see table Electronic Keying
Options.
I. Set the RPI rate.
The RPI must be equal to or greater than
the NUT. This parameter only applies if
the module uses one of the Rack
Optimized communication formats.
J. Inhibit the module, if necessary.
Initially, do you
Then
want the module to
communicate with
the controller?
Yes
Leave the box
unchecked
No
Check the
(1)
box
(1)
When you test this portion of the system,
clear the check box.
2. Configure the 1771-ACN(R)15 module.
K. Determine if you want a major fault on the controller if
the connection to the PanelView fails in Run Mode.
If You Want The
Then
Controller To
fault (major fault)
Select the check box
continue operating
Leave the check box
unchecked
(1)
Monitor the connection using ladder logic.
Control 1771 I/O Over ControlNet
L. Click Finish.
(1)
Publication CNET-UM001C-EN-P - November 2005
D-3
E. Select the module's node
number on ControlNet.
F. Select the Input Size.
G. Select the Output Size.
H. Click Next.