A. Select either a PLC5 Typed Read or PLC5 Typed
Write for the Communication Command.
B. Type the starting address of the data in the
PLC-5 controller.
C. Type the number of elements to read or write.
D. Select Port Number 2 for ControlNet.
E. Type, in quotation marks, the tag name of the
Logix5000 tag.
You can only specify the Logix5000 tag in
quotation marks if the PLC is PLC-5C Series
C/Revision M, Series D/Revision C, Series
E/Revision B, Series F/Revision A or greater.
F. Select Yes for Multihop.
G. Type the node number of the destination
1756-CN2 module.
H. Type the backplane slot number of the
Logix5000 controller.
I. Select No for RSLinx Destination.
Figure 6.1 Configure the Message
Peer-to-Peer Messaging
Publication CNET-UM001C-EN-P - November 2005