Rockwell Automation Allen-Bradley ControlNet 1734-ACNR User Manual page 136

For logix5000 control systems
Table of Contents

Advertisement

8-16
Troubleshoot Your ControlNet Communication Modules
Table 8.7 1784-PCIC, 1784-PCICS and 1784-PKTCS Network Channel Status Indicators
If Both Channel Status
It Means
Indicators Are
Off
No power
1784-PCIC(S) driver not started
1784-PKTCS driver is not installed or the card is
not configured
Faulted card
Channel disabled
Steady red
Faulted card
Alternating red/green
Self-test
Alternating red/off
One of the following:
Steady green
Normal operation
Off
Channel disabled
Flashing green/off
Temporary network errors
Flashing red/off
Media fault
No other nodes present on network
Flashing red/green
Incorrect node address
Incorrect network configuration
(1)
UMAX is the highest node address on a ControlNet network that can transmit data.
Publication CNET-UM001C-EN-P - November 2005
• incorrect node configuration
• duplicate ControlNet node address
Take This Action
Apply power.
1. Start RSLinx software.
2. Verify that the appropriate driver has been configured
properly in RSLinx software.
Install the driver and/or configure the card.
1. Check operating system event log for details of fault (if
the PC's operating system supports an event log).
2. Cycle power to the PC.
3. Verify that you have firmly inserted the card into a PCI
local bus expansion slot and that the expansion slot
screw is tightened.
4. If fault persists, contact your Rockwell Automation
representative or distributor.
Program network for redundant media, if required
1. Check operating system event log for details of fault (if
the PC's operating system supports an event log).
2. Cycle power to the PC.
3. Verify that you have firmly inserted the card into a PCI
local bus expansion slot and that the expansion slot
screw is tightened.
4. If fault persists, contact your Rockwell Automation
representative or distributor.
None
Check card's node address and other ControlNet configuration
parameters.
None
Use RSNetWorx software to configure the ControlNet
network for redundant media, if necessary.
1. Check media for broken cables, loose connectors,
missing terminators.
2. If condition persists, refer to the ControlNet Coax
Media Planning and Installation Manual, publication
and CNET-IN002
1. Check media for broken cables, loose connectors,
missing terminators.
2. If condition persists, refer to the ControlNet Coax
Media Planning and Installation Manual, publication
and CNET-IN002.
Add other nodes to the network.
1. Change card's node address so that it is less than or
(1)
equal to UMAX
.
2. Stop and restart the card's driver in RSLinx software
(1784-PCIC and 1784-PCICS only).
Reconfigure the ControlNet network so that UMAX is greater
than or equal to the card's node address.