Rockwell Automation Allen-Bradley ControlNet 1734-ACNR User Manual page 56

For logix5000 control systems
Table of Contents

Advertisement

3-24
Configure a ControlNet Module
Click Enable
Edits.
A. Select Optimize and re-write
schedule for all connections.
B. Click OK.
Publication CNET-UM001C-EN-P - November 2005
4. Enable edits on the file. When you enable edits, the RSNetWorx for
ControlNet software reads data in the ControlNet modules and builds a
schedule for the network.
5. Save the file. This will schedule and activate the network.
It is always preferable to optimize connections. However,
IMPORTANT
in some cases involving multiple controllers, the Merge
changes... option is available. This option lets controllers
whose connections have not changed to continue
uninterrupted operation. When you merge changes into the
existing schedule, those controllers whose connections
have not changed remain in Run mode rather than
changing to Program mode.
6. In RSLogix 5000 software, save the online project.