This example shows
the default media
configuration of
1000m of RG6
coaxial cable.
Table 3.4 Network Parameters for Scheduling the Network Offline
Parameter
Description
Network
The smallest user-configurable repetitive time cycle in milliseconds at
Update
which data can be sent on ControlNet.
Time (ms)
Max.
This is the node with the highest network address that can use scheduled
Scheduled
time on a ControlNet link. I/O data is transferred during scheduled time.
Address
RSNetWorx for ControlNet software sets this value. We recommend that
you do not change it.
Max.
Node with the highest network address that can use unscheduled time on
Unscheduled
a ControlNet link. Messaging data is transferred during unscheduled time.
Address
Nodes set at addresses higher than the maximum unscheduled node do
not communicate on the network, for example they will not display in
RSLinx software.
Media
Designates if the network uses media redundancy
Redundancy
Network
User-defined name of the network
Name
9. If necessary, change the media configuration. The default media
configuration is sufficient in most cases. However, adjust the
configuration if your network is longer or uses repeaters. If the media
configuration does not accurately represent the maximum propagation
delay between any two nodes, your network may experience errors.
Configure a ControlNet Module