1794-ACN15 and
1794-ACNR15 ControlNet
FLEX I/O Adapters
Table 8.10 1794-ACN15 and 1794-ACNR15 Communication Status Indicators
If Both Channel
It Means
Status Indicators Are
Off
Channel disabled
Steady green
Normal operation
Flashing green/off
Temporary network errors
Node is not configured to go online
Flashing red/off
Media fault
No other nodes present on network
Flashing red/green
Incorrect network configuration
This figure shows the status indicators used on the 1794-ACN15 and
1794-ACNR15 modules.
Figure 8.6 1794-ACN15 and 1794-ACNR15 Status Indicators
Network Channel Status Indicators
This graphic shows a 1794-ACNR15.
The modules use the following 2 status indicators:
• Comm - Communication status indicator for each channel; the
1794-ACN15 module has 1 Comm indicator, and the 1794-ANCR15
module has 2 Comm indicators
• Status - Module status indicator
This table describes the 1794-ACN15 and 1794-ACNR15 communication
status indicators.
Troubleshoot Your ControlNet Communication Modules
Take This Action
Program network for redundant media, if necessary.
None
1. Check media for broken cables, loose connectors,
missing terminators.
2. If condition persists, refer to the ControlNet Coax
Media Planning and Installation Manual, publication
CNET-IN002.
Make sure the network keeper is present and working and
the selected address is less or equal to the UMAX
1. Check media for broken cables, loose connectors,
missing terminators.
2. If condition persists, refer to the ControlNet Coax
Media Planning and Installation Manual, publication
CNET-IN002.
Add other nodes to the network.
Reconfigure the ControlNet network so that UMAX is greater
than or equal to the module's node address.
Publication CNET-UM001C-EN-P - November 2005
8-21
43610
Module Status Indicators