Rockwell Automation Allen-Bradley ControlNet 1734-ACNR User Manual page 109

For logix5000 control systems
Table of Contents

Advertisement

A. Click Logic.
B. Click Map PLC/SLC
Messages.
A. Type the File Number.
B. Type the corresponding
Tag Name from the
RSLogix 5000 project.
Follow these steps to map tags:
1. If the RSLogix 5000 project is online, go offline. You can only map tags
when the project is offline.
2. Access the PLC/SLC Mapping screen.
3. Configure the PLC/SLC Mapping as needed.
When mapping tags:
• Do not use file numbers 0, 1, and 2. These files are reserved for Output,
Input, and Status files in a PLC-5 processor.
• Use PLC-5 mapping only for tag arrays of data type INT, DINT, or
REAL. Attempting to map elements of system structures may produce
undesirable effects.
• Use the PLC file identifier of N or B when accessing elements in an
INT tag array.
Peer-to-Peer Messaging
Publication CNET-UM001C-EN-P - November 2005
6-15