Configure a ControlNet Module
A. Name the remote module.
B. Select the remote module's Node.
C. Select the remote Chassis Size.
D. Select the Slot containing the remote module.
E. Select a Comm Format. For more information
on choosing a Comm Format, see the section
Communication Format.
F. Select the remote module's minor
revision level.
I. Set the RPI rate.
The RPI must be equal to or greater than
the ControlNet Network Update Time
(NUT). This parameter only applies if the
module uses one of the Rack Optimized
communication formats.
J. Inhibit the module, if necessary.
Initially, do you
Then
want the module to
communicate with
the controller?
Yes
Leave the box
unchecked
No
Check the
(1)
box
(1)
When you test this portion of the system,
clear the check box.
Publication CNET-UM001C-EN-P - November 2005
3. Configure the remote ControlNet communication module.
The example below shows configuration for a 1756-CNB
IMPORTANT
module. However, depending on the remote module-type
such as a 1734, 1756, 1769, 1784, 1788, or 1794, there are
differences in how to configure a remote ControlNet
communication module. If you need help configuring a
specific module, use online help in RSLogix 5000 software.
G. Select an Electronic Keying level. For
more information on choosing a keying
level, see the table Electronic Keying
Options.
K. Determine if you want a major fault on the controller if
the connection to the PanelView fails in Run Mode.
If you want the
Then
controller to
fault (major fault)
Select the check box
continue operating
Leave the check box
unchecked
(1)
Monitor the connection using ladder logic.
H. Click Next.
L. Click Finish.