Rockwell Automation Allen-Bradley ControlNet 1734-ACNR User Manual page 142

For logix5000 control systems
Table of Contents

Advertisement

8-22
Troubleshoot Your ControlNet Communication Modules
If Either Channel
It Means
Status Indicators Are
Off
No power
Steady red
Faulted module
Alternating red/green
The module is performing a self-test
Alternating red/off
Incorrect node configuration
(1)
UMAX is the highest node address on a ControlNet network that can transmit data.
Table 8.11 1794-ACN15 and 1794-ACNR15 Module Status Indicators
If The Module Status
It Means
Indicator Is:
Off
Module not communicating due to a power
supply fault or internal fault.
Steady green
Connections established
Flashing green
No connections established
Steady red
Major fault
Flashing red
I/O module removed
Wrong I/O module inserted
FLASH program update in progress
Publication CNET-UM001C-EN-P - November 2005
This table describes the 1794-ACN15 and 1794-ACNR15 module
status indicators.
Take This Action
Apply power.
1. Cycle power.
2. If the fault persists, contact your Rockwell
Automation representative or distributor.
None
Check the module's network address and other ControlNet
configuration parameters.
Take This Action
1. Check the power supply.
2. Check the cable connectors.
3. Make sure the module is properly installed on the
DIN rail.
4. If the indicator remains off, replace the module.
None
Establish connections, if necessary.
1. Cycle power.
2. If the problem persists, replace the daughtercard.
Reinsert the module.
Replace the wrong module with the correct module.
Wait for the program update to finish.