Energizing the Incoming MV Cables

M
f

PHASE CONFORMITY TEST

Serial Light
If the phases matching, light is OFF .
If the phases not maching, light is ON.
(Test device is optional.)

CABLE TEST

Incoming / outgoing switchgear
To check cable faults & insulation
Turn the disconnector OFF .
Turn the earthing disconnector ON.
Open the switchgear front cover.
Place the cable test device (Test rod as optionally.)
Turn the switch OFF .
Perform the required test for check the cable healthy.
f
Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com
I
Voltage Indicator
When MV cables are powered, voltage indicator
lights must be on.
Incoming switchgear
To check cable faults & insulation.
Turn the disconnector OFF .
Switch-OFF the power of the switchgear from previous center
Turn the earthing disconnector ON.
Open the switchgear front cover.
Place the cable test device.
Turn the earthing disconnector OFF from both sides.
Perform the required test.
LBS is ON / OFF
Earthing switch
ON / OFF