Control Terminal Functions - Danfoss VLT FC Series Service Manual

Hide thumbs Also See for VLT FC Series:
Table of Contents

Advertisement

Operator Interface and Driv...

4.8 Control Terminal Functions

Table 4.13 describes the functions of the control terminals. Many of these terminals have multiple functions determined by
parameter settings. Some options provide more terminals.
Terminal
01, 02, 03 and 04, 05, 06
4
4
12, 13
18, 19, 27, 29, 32, 33
20
37
39
42
50
53, 54
55
61
68, 69
Table 4.13 Control Terminals and Functions
Terminal
Parameter
Table 4.14 Control Terminals and Associated Parameters
40
Function
Two Form C output relays. Maximum 240 V AC, 2 A. Minimum 24 V DC, 10 mA, or 24 V AC, 100 mA. Can
be used for indicating status and warnings. Found on the power card.
24 V DC supply to digital inputs and external transducers. The maximum output current is 200 mA.
Digital inputs for controlling the drive. R = 2 kΩ. Less than 5 V = logic 0 (open). Greater than 10 V = logic
1 (closed). Terminals 27 and 29 are programmable as digital/pulse outputs.
Common for digital inputs.
0–24 V DC input for Safe Torque Off (some units).
Common for analog and digital outputs.
Analog and digital outputs for indicating values such as frequency, reference, current, and torque. The
analog signal is 0/4 to 20 mA at a maximum of 500 Ω. The digital signal is 24 V DC at a minimum of 500
Ω.
10 V DC, 15 mA maximum analog supply voltage for potentiometer or thermistor.
Selectable for 0–10 V DC voltage input, R = 10 kΩ, or analog signals 0/4 to 20 mA at a maximum of
200 Ω. Used for reference or feedback signals. A thermistor can be connected here.
Common for terminals 53 and 54.
RS485 common.
RS485 interface and serial communication.
18
19
27
29
5-10
5-11
5-12
5-13
Danfoss A/S © 02/2019 All rights reserved.
®
VLT
FC Series, D1h–D8h, Da2/Db2/Da4/Db4, E1h–E4h, J8/J9
32
33
37
5-14
5-15
5-19
53
54
42
1–3
6-1*
6-2*
6-5*
5-4*
4–6
5-4*
MG94A502

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC Series and is the answer not in the manual?

Questions and answers

Denis mugendi
April 16, 2025

How do I clear log S:28[M26] in my danfoss vfd

Denis
April 16, 2025

How can clear log S:28[M26]in my danfoss vfd

User image 67ff245bb9325
1 comments:
Mr. Anderson
April 16, 2025

To clear log S:28[M26] in your Danfoss VLT FC Series VFD, reset the unit. This clears alarms and warnings, as noted for similar faults like ALARM 78. Make sure the issue causing the log has been resolved before resetting.

This answer is automatically generated

Subscribe to Our Youtube Channel

Table of Contents

Save PDF