13.2.2 Control Card and Control Card Mounting Plate

The control card does not need to be disassembled before the control card mounting plate is removed from the drive. To
remove or replace the control card mounting plate with the card attached, use the following steps. See Illustration 13.1.
Disassembly
1.
Open the front panel door or remove the front
cover, depending on the type of enclosure.
2.
In IP21/IP54 units, unplug the LCP cable.
3.
Unplug the USB connector, if present.
4.
Remove any customer control wiring from the
control card and option cards.
5.
Remove 4 screws (T20) from the corners of the
control card mounting plate.
6.
Unplug the ribbon cable connecting the control
card and power card. To release the cable, press
out on the clasps at each end of the cable
connector on the power card.
MG94A502
Service Guide
NOTICE
UNIQUE TORQUE VALUES
Tighten screws (T20) to the non-standard torque value
specified in the following steps. Tighten remaining
fasteners according to chapter 14.1 Fastener Torque
Ratings.
Reassembly
1.
2.
3.
4.
5.
6.
Danfoss A/S © 02/2019 All rights reserved.
Attach the ribbon cable connecting the control
card to the power card. Click shut the clasps on
each end of the cable connector.
Secure 4 screws (T20) at the corners of the
control card mounting plate. Torque to 2.27 Nm
(20.1 lb-in).
Reconnect any customer control wiring to the
control card and option cards.
In IP21/IP54 units, connect the LCP cable.
Connect the USB, if present.
Reattach the front cover, if present depending on
the enclosure.
13
13
261

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC Series and is the answer not in the manual?

Questions and answers

Denis mugendi
April 16, 2025

How do I clear log S:28[M26] in my danfoss vfd

Denis
April 16, 2025

How can clear log S:28[M26]in my danfoss vfd

User image 67ff245bb9325
1 comments:
Mr. Anderson
April 16, 2025

To clear log S:28[M26] in your Danfoss VLT FC Series VFD, reset the unit. This clears alarms and warnings, as noted for similar faults like ALARM 78. Make sure the issue causing the log has been resolved before resetting.

This answer is automatically generated

Table of Contents

Save PDF