D1h/D3h/D5h/D6h/J8 Drive Di...
10.3 D5h/D6h Disassembly and Assembly
The D5h and D6h drives are D1h drives with extended
options cabinets. The drive profiled here includes a
contactor, disconnect, and brake option, and is 690 V
power range. Some procedures apply to all configurations,
but some vary depending on the size of the enclosure,
extended options cabinet, and selected options.
10.3.1 Accessing the Heat Sink Fan in
D5h/D6h Drives
D5h and D6h drives include an extended options cabinet
mounted below the heat sink fan. To access the heat sink
fan in D5h/D6h drives, remove the busbars between the
main enclosure and the extended options cabinet using
the following steps. In drives with different option configu-
rations, the busbars can vary slightly from the illustrations.
Disassembly
1.
Remove the air baffle covering the interior
components.
2.
Remove the EMC shield by removing 2 screws
(T25).
3.
Remove the 3 mains input jumper busbars (R, S,
and T) between the main enclosure and the
10
10
extended options cabinet. See Illustration 10.29:
3a
3b
178
®
VLT
Remove 3 screws (17 mm) from the top
of the mains input jumper busbars, 1
per busbar.
Remove 3 nuts (13 mm) from the
bottom of the mains input jumper
busbars, 1 per busbar.
Danfoss A/S © 02/2019 All rights reserved.
FC Series, D1h–D8h, Da2/Db2/Da4/Db4, E1h–E4h, J8/J9
1
2
3
1
Screw (17 mm)
2
Mains input jumper busbars
3
Nut (13 mm)
Illustration 10.29 Mains Input Jumper Busbars in D5h/D6h
MG94A502
Need help?
Do you have a question about the VLT FC Series and is the answer not in the manual?
Questions and answers
How do I clear log S:28[M26] in my danfoss vfd
How can clear log S:28[M26]in my danfoss vfd
To clear log S:28[M26] in your Danfoss VLT FC Series VFD, reset the unit. This clears alarms and warnings, as noted for similar faults like ALARM 78. Make sure the issue causing the log has been resolved before resetting.
This answer is automatically generated