5.2 Influencing calculation of the open-loop control and closed-loop control parameters

5.2
Influencing calculation of the open-loop control and closed-loop
control parameters
Using parameter p0500 (technological application), you can influence the calculation of open-
loop control and closed-loop control parameters. The default setting helps you find suitable
values for standard applications.
You can make preassignments for the following technological applications:
Value p0500
100
101
102
103
The value is only used for 1FK2 motors.
1)
An overview of the influenced parameters and the set values is provided in the
"SINAMICS S120/S150 List Manual".
Calling the calculation
You call the calculation of the parameters, which influence the technological application, as
follows:
● When exiting quick commissioning using p3900 > 0
● When automatically calculating the motor/closed-loop control parameters with
p0340 = 1, 3, 5
● When calculating the technology-dependent parameters with p0578 = 1
86
Application
Standard drive (SERVO)
Feed drive (limit current limitation)
Spindle drive (rated current limitation)
Feed drive (maximum power limitation)
1)
Function Manual, 06/2019, 6SL3097-5AB00-0BP2