8.8 dv/dt filter compact plus Voltage Peak Limiter
The maximum permissible pulse frequency when using a du/dt filter:
● For 2.5 kHz
– Chassis power units from 315 kW to 800 kW at 400 V
– Chassis power units from 75 kW to 1200 kW at 690 V
● For 4 kHz
– Chassis power units up to 250 kW at 400 V
Restrictions
The following restrictions must be taken into account when a dv/dt filter is used:
● The output frequency is limited to a maximum of 150 Hz.
● Maximum permissible motor cable lengths:
– Shielded cables: Max. 100 m
– Unshielded cables: Max. 150 m
● Further restrictions are contained in the following device manuals:
– SINAMICS S120 AC Drive
– SINAMICS S120 air-cooled Chassis power units
– SINAMICS S120 Chassis power units, liquid-cooled
Configuring the function
During commissioning, you must activate the dv/dt filter with p0230 = 2.