Motor Mod‐
Rated volt‐
ule frame
age
size
[V]
J
500
600
660
690
J
500
600
660
690
8.14.2

Activating the "Braking Module" function

Requirement
● The STARTER commissioning tool has been opened.
● A new project has been created, or an existing project is opened.
Activating the Braking Module
To activate the braking module and set the operation threshold as well as hysteresis for the
braking module, proceed as follows:
1. Configure the Control Unit and the infeed unit as usual (see SINAMICS S120
Commissioning Manual with STARTER).
2. Select "VECTOR" as drive object type.
3. "U/f control" should be selected as controller structure.
4. In the parameter p1300 (open loop/closed loop control mode of operation), output the value
"15" (operation with braking resistor).
5. Select the supply voltage in the configuration dialog box.
6. Pre-allocate the supply voltage p0210 according to the infeed unit being used (e.g. for a
Basic Line Module with approx. 600 V at 400 V of supply voltage).
7. In the configuration dialog box, select "Chassis" as format.
8. Enter the value "1" in parameter p0864 (infeed unit operation) if the drive line-up is not
equipped with a Basic Line Module.
9. Select the required power unit in the configuration dialog box.
10.Terminate the configuration for the Motor Module and the resistors. Parameter input for
p1360 (Braking Module braking resistance, cold) using the expert list.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Rated
Braking
U
DC link
current
current
chopper
threshold
[A]
[A]
[V]
1025
1020
841
1025
1020
967
1025
1020
1070
1025
1020
1158
1270
1230
841
1270
1230
967
1270
1230
1070
1270
1230
1158
8.14 Motor Module as a Braking Module
Continu‐
Peak
ous brak‐
braking
continuous brak‐
ing power
power
[kW]
[kW]
1050.6
1575.9
1280.0
1812.0
1336.7
2005.0
1446.6
2169.9
1266.9
1900.4
1456.7
2185.1
1611.9
2417.8
1744.5
2616.7
Basic functions
Resistance for
Resistance at
peak braking
ing power
power
[Ω]
[Ω]
0.337
0.224
0.387
0.258
0.428
0.286
0.463
0.309
0.279
0.186
0.321
0.214
0.355
0.237
0.384
0.256