Supplementary conditions
The following supplementary conditions apply to the use of the bypass function:
● The bypass switch is also always shut down if one of the control word signals OFF2 or OFF3
is canceled and the motor coasts down. If the control word signal OFF1 is withdrawn, the
motor remains connected to the supply system.
Exception:
If necessary, the bypass switch can be interlocked by a higher-level controller such that the
converter can be shut down completely (i.e. including the controller electronics) while the
motor is operated on the supply. The contactor interlocking should be implemented on the
plant/system side.
● When the drive is started up again after POWER ON, the status of the bypass contactors is
evaluated. After powering up, the converter can thereby change straight into "Ready to start
and bypass" status. This is only possible if the bypass is activated via a control signal, the
control signal (p1266) is still present once the system has been ramped up, and the
"Automatic restart" function (p1210 = 4) is active.
The bypass is automatically started again when restarting. To accelerate the motor to the
setpoint speed or to synchronize it to the network, the pulse enable may takes place with the
motor rotating. In this case, it is recommended that you activate the "Flying restart" function
(p1200 = 1). This prevents high current peaks.
● Changing the converter into "Ready to start and bypass" status after powering up, is of a
higher priority than switching back on automatically.
● Monitoring of the motor temperatures using temperature sensors is active while the
converter is in one of two states "Ready to start and bypass" or "Ready for operation and
bypass".
● The two motor contactors must be designed for switching under load.
Note
The application examples contained in the following descriptions are only basic circuits
designed to explain the basic principle of operation. The dimensions of specific circuit
configurations (contactors, protective equipment) must be calculated for specific systems.
Commissioning the function
The bypass function is part of the function module "technology controller" that can be activated
when using the commissioning wizard. Parameter r0108.16 indicates whether it has been
activated.