If the Active Line Module is used for reactive power compensation with external reactive current
setpoint, then the reactive current setpoint must also be wired for the slave. The master-to-
slave setpoint specifies only the active current.
When Active Line Modules have been deactivated, make sure that the maximum DC-link
capacitance C
procedure (danger of overloading the pre-charging resistors).
Parameter p3422 (C
closed-loop control can be directly adjusted via this parameter when the Master/Slave
configuration changes, instead of changing the proportional gain of the V
(p3560). When parameter p3422 changes, parameter p3560 is recomputed automatically by
the firmware.
Figure 9-24
Structure diagram: 3 identical Active Line Modules of identical output rating, PROFIBUS communication system
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
for the remaining Active Line Modules is not exceeded during the switch-on
DC link
capacitance) can be changed in operation. This means that the
DC link
ALM1:
p3513 = 1 ( Slave)
ALM2:
p3513 = 1 ( Slave)
p0863.0 = 1
9.9 Master/slave function for Active Infeed
p0863.0 = 0
p0863.0 = 1
Function modules
controller
DC link
p0863.0 = 0