Servo control
5.23 Voltage precontrol
4. Measure a current controller setpoint step change again (see figure below)
Figure 5-40
The measurement result in the example indicates that after reaching the setpoint, the
current decays according to an exponential function (1-exp(-t/Tsm)). You estimate the
smoothing time based on the time from the point of contact of the initial tangent with the final
value straight line.
5. Enter the time constant in p1735.
6. In p1734, enter by what percentage the setpoint point of contact should extend beyond the
final value straight line (e.g. (1.5A/1.32A -1)·100 % = 13.6 %).
200
Example: Prior to optimizing
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Drive functions