Restrictions For Esr - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Procedure
To configure the response for generator operation, proceed as follows:
1. Set the generator operation of the drive with the parameter setting p0888 = 3.
2. Parameterize the V
3. Activate the monitoring of the DC-link voltage for the generator operation with the parameter
setting p1240 = 2.
4. Set the permissible lower voltage limit V
The infeed unit detects when the power fails as the DC-link voltage drops and this is then
signaled as an alarm.
Figure 9-32
9.11.5

Restrictions for ESR

● Operating several axes in the generator mode
Only use one speed-controlled axis to buffer the DC link. If you have parameterized several
axes, faults can occur, which undesirably influence one another and therefore the drive line-
up as a whole.
● Motors that are not suitable for generator operation
Linear motors (1FN) and torque motors (1FW) require an adequately high DC-link voltage
to brake. They are not suitable to buffer the DC link when operating in the generator mode.
● ESR and Safety Integrated
If the Safety Integrated Extended Functions are controlled via PROFIsafe, in the case of a
communication failure, Safety Integrated only permits a response time (p9580/p9380) of
maximum 800 ms. After this time expires, Safety Integrated requests pulse suppression.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
controller.
dc
DC-link voltage setpoint
9.11 Extended stop and retract
of the DC link via parameter p1248.
dc_min
Function modules
537