14.3.4

Error code list

The following table describes error details and corrective actions.
Error
Error
code
category
(decimal)
1
Setting data
range error
2
(Fixed
parameter)
3
10
11
Setting data
range error
12
(Variable
parameter)
13
14
252
Error
Error name
classification
Stroke limit
lower limit
Numerator of
command pulse
multiplication for
electronic gear
Outside the
setting range
Denominator of
command pulse
multiplication for
electronic gear
Outside the
setting range
ERR.1
Speed limit
value Outside
the setting range
Acceleration
time Outside the
setting range
Deceleration
time Outside the
setting range
In-position range
Outside the
setting range
Positioning
mode Outside
the setting range
Operation at the
Description
error occurrence
The set value in
"
Stroke limit
Pr.2
lower limit" is outside -
2147483648 to
"
Stroke limit
Pr.1
upper limit".
The set value in
If a setting is outside
"
Numerator of
Pr.3
the setting range,
command pulse
the error occurs and
multiplication for
all of the fixed
electronic gear" is
parameters use the
outside the setting
default values for
range.
the control.
The set value in
"
Denominator
Pr.4
of command pulse
multiplication for
electronic gear" is
outside the setting
range.
The set value in
"
Speed limit
Pr.5
value" is outside the
setting range.
The set value in
"
Acceleration
Pr.6
time" is outside the
setting range.
The set value in
Only the setting with
the error uses the
"
Deceleration
Pr.7
default value for
time" is outside the
control.
setting range.
The set value in
"
In-position
Pr.8
range" is outside the
setting range.
The set value in
"
Positioning
Pr.9
mode" is other than 0
and 1.
Action
Set a value within the
setting range, and turn
on PLC READY signal
(Y2D).
Set a value within the
setting range, and turn
on PLC READY signal
(Y2D).
[Setting range]
1 to 9999
Set a value within the
setting range, and turn
on PLC READY signal
(Y2D).
[Setting range]
1 to 9999, and besides
1/50 CMX/CDV 50
Set a value within the
setting range.
[Setting range]
10 to 4000000pulse/s
Set a value within the
setting range.
[Setting range]
2 to 9999ms
Set a value within the
setting range.
[Setting range]
2 to 9999ms
Set a value within the
setting range.
[Setting range]
1 to 20479pulse
Set a value within the
setting range.