Item
Alert output
accumulated pulse
Cd.13
setting value (maximum
value)
Description
The difference between the reference value
(maximum value) and the judgment value
(alert output accumulated pulses (maximum
value)) is set.
The relation between this setting and the
judgment value is as follows.
[If "
Accumulated pulse setting value
Cd.17
selection" is set to 0]
Alert output accumulated pulses (maximum
value) = reference value (maximum value) +
Alert output accumulated pulse setting
Cd.13
value (maximum value)
[If "
Accumulated pulse setting value
Cd.17
selection" is set to 1]
Alert output accumulated pulses (maximum
value) = reference value (maximum value) +
(
Alert output accumulated pulse setting
Cd.13
value (maximum value) - 1000) × reference
value (maximum value)  1000
For details on the accumulated pulse error
detection function, refer to the following.
Page 223, Section 11.9
CHAPTER 5 DATA USED FOR POSITIONING
Default
Setting range
• If "
Accumulated
Cd.17
pulse setting value
selection" is set to 0:
1 to 148000 pulse
• If "
Accumulated
Cd.17
0
pulse setting value
selection" is set to 1:
1000 to 50000
-3
(× 10
: Last three digits
are the value after the
decimal point.)
Buffer
memory
value
address
(decimal)
5
400
401
93