Error
Error
code
category
classification
(decimal)
130
131
Accumulated
pulse error
detection
ERR.1
function
error
132
Error
Error name
Accumulated
pulse alert
Accumulated
pulse error
undetectable
Reference value
write error
Operation at the
Description
error occurrence
Accumulated pulses
The positioning
reached the alert
continues.
level.
• The number of
accumulated pulses
used as the
reference of the
accumulated pulse
error detection
function is
unmeasured.
• Either of the values
in "
Alert
Cd.13
output accumulated
pulse setting value
(maximum value)"
and
"
Immediate
Cd.14
stop accumulated
pulse setting value
(maximum value)" is
The accumulated
outside the setting
pulse error detection
range. Moreover,
function is not
either of the values
executed.
in "
Alert
Cd.15
output accumulated
pulse setting value
(minimum value)"
and
"
Immediate
Cd.16
stop accumulated
pulse setting value
(minimum value)" is
outside the setting
range.
• "
Accumulated
Cd.17
pulse setting value
selection" is set to 1
and the
maximum/minimum
reference values
are set to 0.
"
Reference
Cd.20
value write request"
was set to 1 when the
The reference value
measurement was not
is not written to the
being executed
flash ROM.
("
Reference
Md.20
value measurement
flag" was set to 0).
CHAPTER 14 TROUBLESHOOTING
Action
• Measure the
reference value and
then, execute the
accumulated pulse
error detection
function.
• Set the values of
"
Alert output
Cd.13
accumulated pulse
setting value
(maximum value)" to
"
Immediate
Cd.16
stop accumulated
pulse setting value
(minimum value)"
within the setting
range.
• Change the value of
"
Accumulated
Cd.17
pulse setting value
selection" to 0 and
review the setting
values of
"
Alert output
Cd.13
accumulated pulse
setting value
(maximum value)" to
"
Immediate
Cd.16
stop accumulated
pulse setting value
(minimum value)".
Measure the reference
value and then, write
the value.
(Write the value when
"
Reference
Md.20
value measurement
flag" is set to 1.)