Wiring Configuration: Mechanical Brake Control - Danfoss VLT AutomationDrive FC 302 Operating Manual

315-710 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Operating Guide | VLT® AutomationDrive FC 302

7.1.13 Wiring Configuration: Mechanical Brake Control

Table 36: Mechanical Brake Control
Drive
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Danfoss A/S © 2019.12
Parameters
Function
Parameter 5-40 Function Relay
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-11 Terminal 19 Digital Input
Parameter 1-71 Start Delay
Parameter 1-72 Start Function
Parameter 1-76 Start Current
Parameter 2-20 Release Brake Current
Parameter 2-21 Activate Brake Speed [RPM]
* = Default value
Wiring Configuration Examples
Setting
[32] Mech. brake ctrl.
[8] Start*
[11] Start reversing
0.2
[5] VVC+/ FLUX Clockwise
I
m,n
Application dependent
Half of nominal slip of the motor