Operating Guide | VLT® AutomationDrive FC 302
Troubleshooting
Cycle power.
Check that the option is properly installed.
Check for loose or missing wiring.
It may be necessary to contact the Danfoss supplier or service department. Note the code number for further troubleshooting
directions.
Table 41: Internal Fault Codes
Number
Text
0
The serial port cannot be initialized. Contact the Danfoss supplier or Danfoss service department.
256-258
The power EEPROM data is defective or too old. Replace the power card.
512-519
Internal fault. Contact the Danfoss supplier or Danfoss service department.
783
Parameter value outside of minimum/maximum limits.
1024-1284
Internal fault. Contact the Danfoss supplier or Danfoss service department.
1299
The option software in slot A is too old.
1300
The option software in slot B is too old.
1302
The option software in slot C1 is too old.
1315
The option software in slot A is not supported/allowed.
1316
The option software in slot B is not supported/ allowed.
1318
The option software in slot C1 is not supported/ allowed.
1379-2819
Internal fault. Contact the Danfoss supplier or Danfoss service department.
1792
Hardware reset of digital signal processor.
1793
Motor-derived parameters not transferred correctly to the digital signal processor.
1794
Power data not transferred correctly at power-up to the digital signal processor.
1795
The digital signal processor has received too many unknown SPI telegrams. The AC drive also uses this fault code if
the MCO does not power up correctly. This situation can occur due to poor EMC protection or improper grounding.
1796
RAM copy error.
2561
Replace the control card.
2820
LCP stack overflow.
2821
Serial port overflow.
2822
USB port overflow.
3072-5122
Parameter value is outside its limits.
5123
Option in slot A: Hardware incompatible with the control board hardware.
5124
Option in slot B: Hardware incompatible with the control board hardware.
5125
Option in slot C0: Hardware incompatible with the control board hardware.
5126
Option in slot C1: Hardware incompatible with the control board hardware.
5376-6231
Internal fault. Contact the Danfoss supplier or Danfoss service department.
Danfoss A/S © 2019.12
Maintenance, Diagnostics, and
Troubleshooting
AQ275652476278en-000101 / 130R0709| 113