Operating Guide | VLT® AutomationDrive FC 302
Troubleshooting
•
To apply the change, enable option layout changes in parameter 14-89 Option Detection.
•
Alternatively, restore the correct option configuration.
8.4.85 WARNING 89, Mechanical Brake Sliding
Cause
The hoist brake monitor detects a motor speed exceeding 10 RPM.
8.4.86 ALARM 90, Feedback Monitor
Troubleshooting
•
Check the connection to the encoder/resolver option and, if necessary, replace the VLT
Input MCB 103.
8.4.87 ALARM 91, Analog Input 54 Wrong Settings
Troubleshooting
•
Set switch S202 in position OFF (voltage input) when a KTY sensor is connected to analog input terminal 54.
8.4.88 ALARM 99, Locked Rotor
Cause
The rotor is blocked.
Troubleshooting
•
Check if the motor shaft is locked.
•
Check if the start current triggers the current limit set in parameter 4-18 Current Limit.
•
Check if it increases the value in parameter 30-23 Locked Rotor Detection Time [s].
8.4.89 WARNING/ALARM 104, Mixing Fan Fault
Cause
The fan is not operating. The fan monitor checks that the fan is spinning at power-up or whenever the mixing fan is turned on. The
mixing fan fault can be configured as a warning or an alarm in parameter 14-53 Fan Monitor.
Troubleshooting
•
Cycle power to the drive to determine if the warning/alarm returns.