Operating Guide | VLT® AutomationDrive FC 302
8.4.46 WARNING 48, 1.8 V Supply Low
Cause
The 1.8 V DC supply used on the control card is outside of the allowed limits. The supply is measured on the control card.
Troubleshooting
Check for a defective control card.
If an option card is present, check for overvoltage.
8.4.47 WARNING 49, Speed Limit
Cause
The warning is shown when the speed outside of the specified range in parameter 4-11 Motor Speed Low Limit [RPM] and parameter 4-13
Motor Speed High Limit [RPM]. When the speed is below the specified limit in parameter 1-86 Trip Speed Low [RPM] (except when starting
or stopping), the drive trips.
8.4.48 ALARM 50, AMA Calibration Failed
Troubleshooting
Contact the Danfoss supplier or service department.
8.4.49 ALARM 51, AMA Check Unom and Inom
Cause
The settings for motor voltage, motor current, and motor power are wrong.
Troubleshooting
Check settings in parameters 1-20 to 1-25.
8.4.50 ALARM 52, AMA Low Inom
Cause
The motor current is too low.
Troubleshooting
Check the settings in parameter 1-24 Motor Current.
8.4.51 ALARM 53, AMA Motor Too Big
Cause
The motor is too big for the AMA to operate.
116 | Danfoss A/S © 2019.12
Maintenance, Diagnostics, and
Troubleshooting
AQ275652476278en-000101 / 130R0709