CMSX-...-C-U-F1-...
The setpoint value support points have a distance between each other of 5 % of the established set­
point value signal range. From the support points, the user-defined process valve characteristic curve is
generated by connecting 20 line segments (è Fig. 32). The user-defined process valve characteristics
curve is activated with the parameter CHARACTE in the menu CONFIG.(è Section 7.6.6).
1
SPMIN
1
Setpoint position SP [%]
2
Support point (here for analogue setpoint
value 75 %)
Fig. 32
User-defined process valve characteristic curve with 21 support points – example
For the support points, any values can be assigned in rising and falling sequence. Typically, ascending
values are assigned.
44
SPMAX
75
4
%
3
Scaling is dependent on the parameters
SPMIN and SPMAX
4
Analogue setpoint value signal range
Festo – CMSX-...-C-U-F1-... – 1506a English