CMSX-...-C-U-F1-...
After successful initialization has been completed, the display shows the following message:
UserInit
OK
With this, initialization is completed.
9. Briefly press the Set key. Then the command is displayed again in the menu.
*INITIA*
Userinit
10.To switch back to the main menu, briefly press the Set key. The CMSX then displays menu 6 again
MENU
6 INIT
11.If the initial position should be displayed again, press the Set key for approx. 3 s. Then the CMSX
displays the initial position again, e.g.:
−−− 0.0%
VP: 0.0%
7.7.5

Set parameters

Note
Incorrectly set parameters can lead in operation to unexpected behaviour of the con­
nected semi-rotary drive.
• Bring the CMSX into the controller stopped operating status if you wish to avoid
activation of the semi-rotary drive during parameterisation.
• But note that the CMSX can always react to control signals at the control port D-IN
or to changes in the parameter D-IN (è Tab. 16).
After installation and initialization, configuration and parameterisation of the positioner must be ex­
ecuted. Settings and parameters are preset at the plant (delivery status) (è Tab. 5).
Note
If the controller is in operation (operating status Running), the new setting becomes
effective immediately after the Set key is pressed.
Parameter changes become effective immediately after the Set key is pressed. For ex­
ample, digital outputs can change their signal status by changing settings even in the
controller stopped operating status.
• Adjust the parameter values and settings of the device to your application.
• Make the desired settings. Details on the procedure è Section 7.5.
• Test the settings made.
Festo – CMSX-...-C-U-F1-... – 1506a English