CMSX-...-C-U-F1-...
6.2

Pneumatic installation

Caution
Despite switched-off compressed air supply – dependent on the product variant – one
or both working ports of the positioner can remain under pressure.
• Vent the working ports with the help of the Sensor function (menu 1) before you
remove the tubing lines (è Section 7.6.5).
Note
Use suitable fittings (G1/8) and tubes.
Recommendation: Push-in fittings of type QS-1/8-...-I and tubes of type PUN.
Prior to the pneumatic installation:
1. Ensure there is no voltage or pressure applied.
2. Secure the system against being switched back on.
1
Supply port
2
Working port 2
3
Working port 4
Fig. 14
Pneumatic connections
1. Switch off the compressed air and power supplies.
2. Connect working port 2 2 and working port 4 3 to the working ports of the semi-rotary drive.
Only connect working port 2 for single-acting drives.
– Keep tubing short.
3. Connect supply port 1 to the compressed air source.
4. Screw an appropriate silencer into the exhaust port 6.
Festo – CMSX-...-C-U-F1-... – 1506a English
5
6
1
4
3
4
5
6
QS push-in fitting (accessories)
Silencer (accessory)
Exhaust port
2
17