7.7.4

Executing the user-guided initialization (Userinit)

With user-guided initialization, each individual step of initialization is started by pressing the Add but­
ton by hand. The drive is moved thereby!
Note
During initialization, the process valve is moved to the physical end positions.
• Execute initialization only during the commissioning phase.
Execute user-guided initialization as follows:
1. Activate the compressed air supply.
2. Switch on the operating voltage. The CMSX then displays the initial position, e.g.:
−−− 0.0%
VP: 0.0%
3. Press the Set key for approx. 3 s. The CMSX then displays the first menu.
MENU
1 Sensor
4. Briefly press the Sub key. Then the CMSX shows the menu 6. Alternatively, you can also press the
Add key 5 times to switch from menu 1 to menu 6.
MENU
6 INIT
5. To open the menu, briefly press the Set key. The first command in the menu is then displayed.
*INITIA*
Autoinit
6. To switch further to the next command, briefly press the Add key.
*INITIA*
Userinit
7. To start user-guided automatic initialization, hold down the Set and Add keys simultaneously for
approx. 3 seconds. The first steps of initialization are shown on the display.
UserInit
11-- 1
To start the displayed initialization step, briefly press the Add key. The step will then be executed.
The drive is moved. After the step is completed, the next initialization step is displayed.
UserInit
11-- 2
8. Press the Add key briefly each time until all steps have been executed.
52
Festo – CMSX-...-C-U-F1-... – 1506a English