7.6.6

Menu configuration (2)

Display
Description
MENU 2 CONFIG
Establishes the active setpoint value input and the type of setpoint value signal
SIGNAL
0-10 V
4-20 mA
0-20 mA
1)
Specifies in which direction the process valve opens (semi-rotary drives only).
Open
clockwis
anti-clk
Establishes the signal direction for increasing the setpoint position (SP) (è Fig. 25).
DIRECT
increase
decrease
Character of the setpoint value characteristics curve
CHARACTE
linear
1 : 25
1 : 33
1 : 50
user-def
D-OUT-1
Establishes the behaviour of the two status outputs (D-OUT-1, D-OUT-2).
D-OUT-2
power-H
power-L
limit1-H
limit1-L
limit2-H
limit2-L
limits-H
limits-L
stop-H
stop-L
Establishes the reaction to a signal at the digital input D-IN. The controller is then
D-IN
inactive. Either both of the working ports of the device are pressurized in order to
stop or one working port is pressurized and one is exhausted.
stop-H
stop-L
lmt1-H
lmt1-L
lmt2-H
lmt1-L
1) Submenu only available for CMSX-S-... (rotary)
Tab. 16
Menu configuration (2)
34
Voltage input (pin 1, 2); 0 ... 10 V
Current input (pin 3, 4); 4 ... 20 mA (presetting)
Current input (pin 3, 4); 0 ... 20 mA
Clockwise
Anti-clockwise (presetting)
Increasing setpoint value signal (presetting)
Decreasing setpoint signal
Linear characteristic curve (presetting); linear ratio between ana­
logue setpoint value and setpoint position (è Fig. 26)
Equal-percentage characteristic curve (è Fig. 26)
User-defined setpoint value characteristic curve (è Section 7.6.8)
High level if load voltage supply is present for outputs
Low level if load voltage supply is present for outputs (presetting)
High level, if end position 1 is reached
Low level, if end position is 1 reached
High level, if end position 2 is reached
Low level, if end position 2 is reached
High level, if end position 1 or end position 2 is reached
Low level, if end position 1 or end position 2 is reached
High level, if CMSX is in the operating status "Actuat stopped"
Low level, if CMSX is in the operating status "Actuat stopped"
In the case of High level, stop drive (presetting)
In the case of Low level, stop drive
In the case of High level, travel to stop 1
In the case of Low level, travel to stop 1
In the case of High level, travel to stop 2
In the case of Low level, travel to stop 2
Festo – CMSX-...-C-U-F1-... – 1506a English