Danfoss VLT Series Programming Manual page 71

Hvac drive
Hide thumbs Also See for VLT Series:
Table of Contents

Advertisement

Parameter Description
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
3
3
The selection of each mechanical relay is realised in an array
parameter.
Option:
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[84]
SL digital output E
[85]
SL digital output F
[160]
No alarm
[161]
Running reverse
[165]
Local ref active
[166]
Remote ref active
[167]
Start command act.
[168]
Hand / Off
[169]
Auto mode
[180]
Clock Fault
[181]
Prev. Maintenance
[188]
AHF Capacitor Connect
[189]
External Fan Control
[190]
No-Flow
[191]
Dry Pump
[192]
End Of Curve
[193]
Sleep Mode
[194]
Broken Belt
[195]
Bypass Valve Control
[196]
Fire Mode
[197]
Fire Mode was Act.
[198]
Drive Bypass
[211]
Cascade Pump 1
[212]
Cascade Pump 2
[213]
Cascade Pump 3
5-41 On Delay, Relay
Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
0.01 s
[0.01 - 600.00 s] Enter the delay of the relay cut-in
*
70
®
VLT
HVAC Drive Programming Guide
Function:
Function:
time. Select one of available
mechanical relays and MCB 105 in an
MG.11.CC.02 - VLT
5-41 On Delay, Relay
Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Selected
Event
Relay
output
On Delay
P 5-41
Selected
Event
Relay
output
On Delay
P 5-41
5-42 Off Delay, Relay
Array [9] (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
0.01 s
[0.01 - 600.00 s] Enter the delay of the relay cut-out
*
Selected
Event
Relay
output
On Delay
P 5-41
If the selected Event condition changes before the on- or
off delay timer expires, the relay output is unaffected.
®
is a registered Danfoss trademark
Function:
array function. See 5-40 Function Relay.
Relay 3-6 are included in MCB 113.
O Delay
P 5-42
Function:
time. Select one of available
mechanical relays and MCB 105 in an
array function. See 5-40 Function Relay.
O Delay
P 5-42

Advertisement

Table of Contents
loading

Table of Contents