Danfoss VLT Series Programming Manual page 73

Hvac drive
Hide thumbs Also See for VLT Series:
Table of Contents

Advertisement

Parameter Description
3.7.7 5-6* Pulse Outputs
Parameters for configuring the scaling and output
functions of pulse outputs. The pulse outputs are
designated to terminals 27 or 29. Select terminal 27 output
3
3
in 5-01 Terminal 27 Mode and terminal 29 output in
5-02 Terminal 29 Mode.
Output value
High output
value
P 5-60(term27)
P 5-63(term29)
Options for readout output variables:
[0]
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque relative to limit
[105]
Torque relative to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop
[114]
Ext. Closed Loop
[115]
Ext. Closed Loop
Select the operation variable assigned for terminal 27
readouts.
This parameter cannot be adjusted while the motor is
running. Same options and functions as parameter group
5-6*.
[0]
*
5-60 Terminal 27 Pulse Output Variable
Option:
[0]
No operation
*
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[90]
kWh counter pulse
72
VLT
High freq.
P 5-62(term27)
P 5-65(term29)
No operation
Function:
MG.11.CC.02 - VLT
®
HVAC Drive Programming Guide
5-60 Terminal 27 Pulse Output Variable
Option:
[100]
[101]
[102]
[103]
[104]
[105]
[106]
[107]
[113]
[114]
[115]
5-62 Pulse Output Max Freq #27
Set the maximum frequency for terminal 27, corresponding to
the output variable selected in 5-60 Terminal 27 Pulse Output
Variable.
This parameter cannot be adjusted while the motor is running.
Output
Range:
(Hz)
5000 Hz
*
5-63 Terminal 29 Pulse Output Variable
Select the variable for viewing on the terminal 29 display.
This parameter cannot be adjusted while the motor is running.
Same options and functions as parameter group 5-6*.
Option:
[0]
*
[45]
[48]
[90]
[100]
[101]
[102]
[103]
[104]
[105]
[106]
[107]
[113]
[114]
[115]
5-65 Pulse Output Max Freq #29
Set the maximum frequency for terminal 29 corresponding to the
output variable set in 5-63 Terminal 29 Pulse Output Variable.
This parameter cannot be adjusted while the motor is running.
Range:
5000 Hz
*
®
is a registered Danfoss trademark
Output freq. 0-100
Reference Min-Max
Feedback +-200%
Motor cur. 0-Imax
Torque 0-Tlim
Torque 0-Tnom
Power 0-Pnom
Speed 0-HighLim
Ext. Closed Loop 1
Ext. Closed Loop 2
Ext. Closed Loop 3
Function:
[0 - 32000 Hz]
No operation
Bus ctrl.
Bus ctrl., timeout
kWh counter pulse
Output freq. 0-100
Reference Min-Max
Feedback +-200%
Motor cur. 0-Imax
Torque 0-Tlim
Torque 0-Tnom
Power 0-Pnom
Speed 0-HighLim
Ext. Closed Loop 1
Ext. Closed Loop 2
Ext. Closed Loop 3
Function:
[0 - 32000 Hz]
Function:
Function: